{"product_id":"apollo-din-rail-input-output-unit-sa4700-302apo","title":"Apollo Fire Alarm Interface Unit, Intelligent DIN-Rail Input\/Output, 1A Relay SA4700-302APO","description":"\u003cp\u003eThe Apollo SA4700-302APO is a fire alarm interface unit that lets an addressable loop monitor volt free contacts and switch a changeover relay. It suits installers linking other equipment to a fire system. It mounts on a 35 mm DIN-rail and works with XP95, Discovery and CoreProtocol communication.\u003c\/p\u003e\u003ch2\u003eKey features\u003c\/h2\u003e\u003cul\u003e\n\u003cli\u003eWatches outside equipment – supervises one or more normally open volt free contacts on a single pair of cables\u003c\/li\u003e\n\u003cli\u003eSwitches other equipment – changeover relay output contacts rated 1 A at 30 V dc or ac\u003c\/li\u003e\n\u003cli\u003eA set state if the loop is lost – Failsafe Mode activates the relay on loss of loop or protocol loss, and meets BS 7273-4 requirements\u003c\/li\u003e\n\u003cli\u003eTidy in a panel or enclosure – designed for a 35 mm width DIN-Rail, 33 mm height x 102 mm width x 33 mm depth\u003c\/li\u003e\n\u003cli\u003eQuick to wire – improved design for ease of wiring meaning faster installation\u003c\/li\u003e\n\u003cli\u003eStatus at a glance – separate LEDs for the relay, polling and isolator state, and the input\u003c\/li\u003e\n\u003c\/ul\u003e\u003ch2\u003eFor installers\u003c\/h2\u003e\u003cul\u003e\n\u003cli\u003ePower: supply voltage 17–35 V dc. Quiescent current 500 µA, max current LEDs on 3.5 mA.\u003c\/li\u003e\n\u003cli\u003eMounting: on a 35 mm width DIN-Rail inside an enclosure. Not designed for outdoor use unless mounted in a suitable weatherproof enclosure.\u003c\/li\u003e\n\u003cli\u003eCabling: volt free contacts on a single pair of cables, plus changeover relay contacts rated 1 A at 30 V dc or ac. See Installation Guide 39215-160.\u003c\/li\u003e\n\u003cli\u003eCompatibility: XP95, Discovery and CoreProtocol compatible, fire control panel dependant.\u003c\/li\u003e\n\u003cli\u003eStandards: EN 54-17, EN 54-18, CPR, LPCB, VdS, BOSEC, SBSC, FG. Failsafe Mode meets BS 7273-4 requirements.\u003c\/li\u003e\n\u003c\/ul\u003e\u003cdiv class=\"mt-6\"\u003e\n\u003ch3\u003eFrequently asked questions\u003c\/h3\u003e\n\u003ch4 class=\"product-description-title\"\u003eCan the relay switch mains?\u003c\/h4\u003e\n\u003cp\u003eNo, not directly. The relay output contact rating is 1 A at 30 V dc or ac.\u003c\/p\u003e\n\u003ch4 class=\"product-description-title\"\u003eWhat does failsafe mode do?\u003c\/h4\u003e\n\u003cp\u003eIt activates the on-board relay without a command from the control panel when the loop or protocol is lost. It is selected with a DIL switch.\u003c\/p\u003e\n\u003ch4 class=\"product-description-title\"\u003eCan it be fitted outdoors?\u003c\/h4\u003e\n\u003cp\u003eOnly in a suitable weatherproof enclosure. On its own the unit is not designed for outdoor use.\u003c\/p\u003e\n\u003ch4 class=\"product-description-title\"\u003eWhich protocols does it work with?\u003c\/h4\u003e\n\u003cp\u003eXP95, Discovery and CoreProtocol, depending on the fire control panel. On XP95 and Discovery it behaves as an XP95 device, and on CoreProtocol as a Soteria device.\u003c\/p\u003e\n\u003ch4 class=\"product-description-title\"\u003eDoes every panel get all the modes?\u003c\/h4\u003e\n\u003cp\u003eNo. The nine pre-configured modes are a CoreProtocol enabled systems feature only, so check the panel's documentation.\u003c\/p\u003e\n\u003c\/div\u003e","brand":"Apollo Fire","offers":[{"title":"Default Title","offer_id":57710605664629,"sku":"SA4700-302APO","price":53.23,"currency_code":"GBP","in_stock":true}],"thumbnail_url":"\/\/cdn.shopify.com\/s\/files\/1\/0050\/1216\/0612\/files\/apollo-sa4700-302apo-din-rail-input-output-unit-angled-view.jpg?v=1793615599","url":"https:\/\/wmestore.co.uk\/products\/apollo-din-rail-input-output-unit-sa4700-302apo","provider":"WME","version":"1.0","type":"link"}