{"product_id":"apollo-discovery-heat-detector-58000-400apo","title":"Apollo Discovery Heat Detector, Addressable, Five Response Modes, White 58000-400APO","description":"\u003cp\u003eThe Apollo Discovery 58000-400APO is a heat detector for addressable fire alarm systems on the Discovery protocol. It senses air temperature, not smoke, so Apollo rates it well suited to kitchens and smoking rooms. It offers five EN54 approved response modes, runs on 17 - 28 V dc and is rated IP44.\u003c\/p\u003e\u003ch2\u003eKey features\u003c\/h2\u003e\u003cul\u003e\n\u003cli\u003eCopes with fumes and dirt – for environments that are dirty or smoky under normal circumstances\u003c\/li\u003e\n\u003cli\u003eMatches the room – five EN54 approved response modes, selected through the fire control panel\u003c\/li\u003e\n\u003cli\u003eReads the air temperature – a single NTC thermistor, sampled once per second\u003c\/li\u003e\n\u003cli\u003eEasy to see in alarm – two red LEDs, with an optional remote LED\u003c\/li\u003e\n\u003cli\u003eTested from the panel – on command the detector is forced electrically into alarm\u003c\/li\u003e\n\u003cli\u003eFewer false alarms – low sensitivity to very rapid changes in the sensor output\u003c\/li\u003e\n\u003c\/ul\u003e\u003ch2\u003eFor installers\u003c\/h2\u003e\u003cul\u003e\n\u003cli\u003ePower: 17 - 28 V dc on the two wire loop. Quiescent 400 µA, power-up surge 1mA, maximum power-up time 10 seconds.\u003c\/li\u003e\n\u003cli\u003eMounting: 100 mm diameter x 42 mm height, 105 g. Connections are in the mounting base.\u003c\/li\u003e\n\u003cli\u003eCabling: L1 and L2 for the incoming and outgoing supply, +R and -R for a remote indicator. Two wire supply, polarity insensitive.\u003c\/li\u003e\n\u003cli\u003eCompatibility: Discovery (XP95 and CoreProtocol compatible). Ask your chosen panel manufacturer about system compatibility and feature support.\u003c\/li\u003e\n\u003cli\u003eStandards: EN 54-5, CPR, LPCB, VdS, BOSEC, SBSC, CCMG, Kazakhstan. IP44.\u003c\/li\u003e\n\u003c\/ul\u003e\u003cdiv class=\"mt-6\"\u003e\n\u003ch3\u003eFrequently asked questions\u003c\/h3\u003e\n\u003ch4 class=\"product-description-title\"\u003eWhich response mode should be chosen?\u003c\/h4\u003e\n\u003cp\u003eChoose by the temperature the room normally reaches. Modes 1 to 3 suit an application temperature of 25°C typical and 50°C maximum, and Modes 4 and 5 suit 55°C typical and 80°C maximum.\u003c\/p\u003e\n\u003ch4 class=\"product-description-title\"\u003eCan it go in a kitchen?\u003c\/h4\u003e\n\u003cp\u003eYes. Apollo rates it well suited to kitchens and smoking rooms, because it senses heat and not smoke particles. Pick the response mode to match the room.\u003c\/p\u003e\n\u003ch4 class=\"product-description-title\"\u003eDoes it work with XP95 panels?\u003c\/h4\u003e\n\u003cp\u003eIt is Discovery, and XP95 and CoreProtocol compatible. Apollo sends buyers to the chosen panel manufacturer for system compatibility and feature support, so check there first.\u003c\/p\u003e\n\u003ch4 class=\"product-description-title\"\u003eAt what temperature does it alarm?\u003c\/h4\u003e\n\u003cp\u003eThat depends on the mode. Static response temperature runs from 54°C minimum in Modes 1 to 3 up to 100°C maximum in Modes 4 and 5.\u003c\/p\u003e\n\u003ch4 class=\"product-description-title\"\u003eCan it be tested without heat?\u003c\/h4\u003e\n\u003cp\u003eYes, from the panel. The remote test feature forces the detector electrically into alarm on a command from the fire control panel.\u003c\/p\u003e\n\u003c\/div\u003e","brand":"Apollo Fire","offers":[{"title":"Default Title","offer_id":57714822218101,"sku":"58000-400APO","price":40.85,"currency_code":"GBP","in_stock":true}],"thumbnail_url":"\/\/cdn.shopify.com\/s\/files\/1\/0050\/1216\/0612\/files\/apollo-58000-400apo-discovery-heat-detector-angled-view.jpg?v=1793701398","url":"https:\/\/wmestore.co.uk\/products\/apollo-discovery-heat-detector-58000-400apo","provider":"WME","version":"1.0","type":"link"}