{"product_id":"haes-technologies-processor-zone-pcb-tpca01-x4mar","title":"Haes Technologies TPCA01-X4MAR processor zone PCB, Silver","description":"\u003cp\u003e\u003cstrong\u003ePlease note: this is a non-returnable item (excluding faulty goods)\u003c\/strong\u003e\u003c\/p\u003e\n\u003cp\u003e\u003cstrong\u003eHaes Technologies TPCA01-X4MAR is a processor zone PCB.\u003c\/strong\u003e\u003c\/p\u003e\n\u003cp\u003eMain PCB for Esento Marine 12 Zone Conventional panels.\u003c\/p\u003e\n\u003ch3\u003eKey features\u003c\/h3\u003e\n\u003cul\u003e\n\u003cli\u003ePower supply voltage control line, for temperature compensation control\u003c\/li\u003e\n\u003cli\u003e28V DC supply input, diode protected for reversal and independent short circuit, maximum current 3A\u003c\/li\u003e\n\u003cli\u003eMaximum input current 3A, input voltage 22VDC to 32VDC\u003c\/li\u003e\n\u003cli\u003e4 Fire alarm zone circuits\u003c\/li\u003e\n\u003cli\u003eConventionally wired detection circuit\u003c\/li\u003e\n\u003cli\u003eMaximum 32 detectors per zone\u003c\/li\u003e\n\u003cli\u003eMonitoring current limit 50mA, fused at 500mA; typical maximum load 22 alarm devices at 18mA each per circuit\u003c\/li\u003e\n\u003c\/ul\u003e\n\u003cp\u003eIf you are matching this to an existing installation, work from the TPCA01-X4MAR part number rather than the description.\u003c\/p\u003e","brand":"Haes Technologies","offers":[{"title":"Default Title","offer_id":57603710943605,"sku":"TPCA01-X4MAR","price":208.44,"currency_code":"GBP","in_stock":true}],"thumbnail_url":"\/\/cdn.shopify.com\/s\/files\/1\/0050\/1216\/0612\/files\/TPCA01-X4MAR.jpg?v=1790204396","url":"https:\/\/wmestore.co.uk\/products\/haes-technologies-processor-zone-pcb-tpca01-x4mar","provider":"WME","version":"1.0","type":"link"}