Panels
XFP 2 loop 32Z CAST
C-TEC XFP502/CA XFP 2 loop 32 Zone Panel, C-TEC CAST. Max. 2 x 7Ah batteries
C-TEC’s tried and trusted XFP two loop 32 zone addressable fire alarm panel – now available with C-TEC’s own digital fire alarm system protocol, CAST and fully certified to EN54 parts 2, 4 & 13.
With two powerful 40V 450mA loop drivers allowing the connection of up to 255 CAST devices per loop, the installation of a robust, feature-packed addressable fire alarm system has never been easier.
Protocol Features
‘CAST’ is the world’s most-advanced ‘distributed intelligence’ fire alarm system protocol. Conceived, designed and realised by C-TEC as part of a five-year, multi-million pound project, it involved the creation of a powerful proprietary communication protocol (C-TEC Addressable System Technology, CAST) and multiple control panels & field devices. Key features include:
• 255 devices per loop.
• Autonomous decision-making for faster response times.
• Multiple type codes.
• 40V loop drive voltage.
• Two ‘soft’ addressing options – automatic via the panel or manual via a powerful handheld programmer.
• Powerful multi-level addressing facilitates easy device addition and swapped device identification.
• Multiple functionality at a single address (integrated devices) – due 2021.
• Volumes, tones & detector modes can be changed at compatible panels.
• High-speed data transmission and robust data transfer.
• Provides geographical location of short and open circuit faults (a short circuit isolator is included as standard in every CAST field device).
• Replace device function.
• Programmable multi-function status LED.
• Future seamless integration with other CAST life safety systems reducing energy, servicing, installation and repair costs.
• ENVISION Enabled – fully compliant with our new ENVISION Cloud-based Fire ‘IoT’ Remote Access, System Test and Site Management software package.
• Designed and manufactured in the UK.
Panel Features
• Certified to EN54-2/4 by the Loss Prevention Certification Board (LPCB) and EN54-13 by Kiwa Telefication.
• Two independently programmable conventional sounder circuits.
• Two programmable inputs.
• A fault output relay and three programmable relay outputs with voltage free changeover contacts.
• A selection of zone dependency/coincidence functions.
• A day/night (building occupied/unoccupied) function.
• An investigation delay period function.
• Phased evacuation facility.
• An alarm counter that records how many times the panel has been in alarm state.
• Powerful short circuit protected loop drivers.
• An integral EN54-4/A2 switch mode.
• Adjustable contamination levels.
• Earth fault monitoring.
• Combined keypad / keyswitch entry to Access Levels 2 and 3.
• 500 event monitoring.
• An intuitive Windows based upload-download PC program.
• Up to eight XFP main panels (any variant) can be connected onto a two-wire RS485 non-redundant network. Alternatively, up to eight XFP repeaters can be connected to any non-networked main panel.
CFP ECO 8 zone panel CFP708E-4
- Third-party certified to EN54 parts 2 and 4 by the Loss Prevention Certification Board (LPCB) with optional EN54 part 13 compliance from the BSI.
- Intuitive user-friendly interface with colour-coded buttons and combined keypad/keyswitch entry.
- Manufactured by C-TEC in the UK.
- Two detector zone circuits.
- Four conventional sounder circuits
- Integral 1.5A EN54-4/A2 compliant switch mode PSU.
- Wide range of engineering functions including zone test, coincidence, zone delay and non-latching zones.
- Two on-board relays (Fire and Fault).
- Two open-collector outputs (Remote and Reset).
- ‘Class change’ and alert inputs.
- Installer-friendly design.
- Attractive flush or surface mountable plastic lid and enclosure – no bezel required.
- Low 25mA quiescent current.
- Multiple indicators.
- System expansion connections provided for up to eight two-wire repeaters (one CFP761 network card required per system), optional CFP relay boards and optional EN54-13 compliant sounder circuit boards.
- Space for two x 12V 3.3Ah VRLA batteries.
- Fully compatible with C-TEC’s ActiV range of conventional fire detectors.