Advanced Go Addressable Fire Alarm Panel, 1 Loop, Apollo/Hochiki, 50 Addresses GO1
About this product
The Advanced GO1 is a single loop fire alarm panel for non-networked addressable systems using Apollo or Hochiki devices. It suits smaller sites and the installers who commission them. It takes 50 addresses on its one loop and has 15 built-in zone LEDs, so no separate zone card is needed.
Key features
- Sized for a smaller single loop – 50 addresses on Apollo/Hochiki
- See where the alarm is without an extra card – integral zonal LEDs, 15 of them, with 35 additional software indication zones
- Quicker to commission – auto-learn, loop detection and an on-board scope facility
- A long record for fault-finding – 5000 events with diagnostics + 500 fire events
- Outputs on the board – 2 programmable sounder outputs sharing 1 A in total, and three relay outputs
- Easier first fix – a 'no hinge' removable door and hangable chassis
- Clear to operate – a backlit 240x64 graphical LCD with a 12-button alpha-numeric keypad
For installers
- Power: AC supply 220-240 V, 50–60 Hz, 1.0 A max. Battery capacity 24 V 4 Ah internal (min), 24 V 7 Ah internal (max).
- Mounting: steel IP30 enclosure, H x W x D 345x345x87 mm, 4 kg excluding batteries.
- Cabling: 14x20mm knockouts at top. USB type B for direct PC connection.
- Compatibility: Apollo (XP95, Discovery) and Hochiki (ESP) devices. Routing needs a P-Bus adaptor and a routing card. Options include the GOP-001 PBUS Adaptor Card, MXP-532 Routing/Protection Interface and MXP-506 Routing Termination Card.
- Standards: EN54-2:1997+A1:2006 and EN54-4:1997+A1:2002+A2:2006, among its listings.
Frequently asked questions
How many devices can the GO1 take?
50 addresses, on one loop. That applies to Apollo or Hochiki devices.
Which detector protocols does it support?
Apollo (XP95, Discovery) and Hochiki (ESP). A protocol is the digital language a panel and its devices must share, so check yours before ordering.
Can it be networked to other panels?
No. Network is None, and the series is for non-networked single-loop systems.
Can it be programmed without a laptop?
Yes. It is fully programmable on site through the control panel display, or with the PC Configuration Tool.
What batteries does it take?
24 V 4 Ah internal (min) up to 24 V 7 Ah internal (max). The 4 kg weight excludes batteries.
-
Download
- GO1 datasheet
Specifications
Dimensions
Specifications
| Brand | Advanced |
|---|---|
| Model | GO1 |
| Manufacturer Part Number (MPN) | GO1 |
| Also listed as | Go1 |
| Product type | Single Loop Fire Alarm Control Panel |
| Order code description | Go1 1 loop fire panel - Grey (Apollo/Hochiki: 50 addresses) |
| Protocols | Apollo (XP95, Discovery), Hochiki (ESP) |
| Number of loops | 1 |
| Loop current | 500 mA max |
| Number of fire zones | 50 max |
| Zone LEDs | Integral 15 zone LEDs, with 35 additional software indication zones |
| Relay outputs | 3x1A 30VAC/DC (max) to 10mA 5V (min) |
| Auxiliary output | 24 V DC, 100 mA (with GOP-001 fitted) |
| Display | LCD white backlit 240x64 graphical LCD |
| Programmable inputs | 1 x key switch, 1 x monitored |
| USB | USB type B interface for PC connection |
| Network | None |
| Event log | 5000 events with diagnostics + 500 fire events |
| Enclosure | Steel IP30 RAL7035 |
| Dimensions | H x W x D 345x345x87 mm |
| Weight | 4 kg excluding batteries |
| Temperature range | -5°C to 40°C |
| Humidity (RH) | 95% max |
| Cable entries | 14x20mm knockouts at top |
| AC supply | 220-240 V, 50–60 Hz, 1.0 A max |
| Safety | EN62368-1, Class 1, Pollution Degree 2, Overvoltage Category II |
| Battery capacity | 24 V 4 Ah internal (min), 24 V 7 Ah internal (max) |
| Charging current | 0.35 A temp compensated |
| Deep discharge cut-off | 19.5 V |
| Power supply | On-board 24 V DC, 1.5 A high efficiency off-line switched mode |
| Output voltage | 18.0 V–28.0 V |
| Ripple | Up to 1.0 V (Vpkpk) |
| Max battery ohms | 1.8 Ω ± 0.1 Ω |
| Imax(a), Imax(b) | 1.15 A, 1.5 A |
| Listings and approvals | EN54-2:1997+A1:2006, EN54-4:1997+A1:2002+A2:2006, EN61000-3-2:2014, EN61000-3-3:2013, EN50130-4:2011+A1:2014, EN55032:2015, EN62368-1:2014+A11:2017, EN IEC63000:2018 |
| EN54-13 | Meets EN54-13 (2005) Clauses 5.3.4.1 and 5.3.4.2 (partial open and short circuits) |
Dimensions
| Dimensions | H x W x D 345x345x87 mm |
|---|
Advanced Go Addressable Fire Alarm Panel, 1 Loop, Apollo/Hochiki, 50 Addresses GO1