Advanced MxPro 5 Addressable Fire Alarm Panel, 2-8 Loop, Nittan Evolution MX-5802N
About this product
The Advanced MX-5802N is a 2-8 loop fire alarm control panel from the MxPro 5 series, for Nittan Evolution protocol devices. It suits larger and multi-area sites. It comes with 2 loop cards, expands to 8 loops, and has 8 onboard sounder circuits and 20 programmable zonal LEDs.
Key features
- Starts at two loops and grows – 2 loop cards as standard, expandable to 8
- Plenty of alarm outputs – 8 programmable 1 Amp sounder circuits
- Clear to read and operate – white backlit 240 x 64 graphical LCD and keypad
- Shows where the fire is – 20 programmable zonal LEDs with slide-in labels, plus 25 system LEDs
- Networks with other MxPro 5 and MxPro 4 panels – peer-to-peer, standard network version
- Easier commissioning – Auto-learn, loop detection and onboard scope
For installers
- Power: 200-240v 47-63Hz AC mains, 1.4A max; charger 2 x 2.0A temperature compensated; 2 x 5A maximum total for loops, sounders and auxiliary supplies.
- Mounting: steel IP30 enclosure in RAL7035, 750 x 450 x 190 mm (H x W x D), with a removable equipment chassis and plug-in connectors.
- Cabling: 20mm knockouts, 30 top, 6 top rear, 2 bottom rear and 3 bottom; loops at 500mA max each; 2 x 24v 500mA auxiliary supplies.
- Compatibility: Nittan Evolution protocol devices; devices per loop are protocol dependent.
- Standards: EN54-2:1997+AC:1999+A1:2006 and EN54-4:1997+AC:1999+A1:2002+A2:2006.
Frequently asked questions
Which detectors does the MX-5802N work with?
Nittan Evolution protocol devices. Other protocols in the MxPro 5 range use different order codes, such as MX-5802A or MX-5802V.
How many loops come with it?
Two loop cards come as standard. For more loops, add one loop driver card per extra loop, up to 8.
Which loop card adds a loop?
The MXP-567 loop driver card, which is the Nittan version.
What batteries does it take?
From 24v 4Ah up to one 24V 45Ah battery inside, and a second 24V 45Ah battery in an optional external battery enclosure.
How many fire zones does it support?
Up to 400 across 8 loops, and up to 2000 when networked.
-
Download
- MX-5802N datasheet
Specifications
Dimensions
Specifications
| Brand | Advanced |
|---|---|
| Model | MX-5802N |
| Manufacturer Part Number (MPN) | MX-5802N |
| Product | 2-8 loop fire alarm control panel, MxPro 5 series |
| Protocol (this order code) | Nittan Evolution |
| Network version | Standard |
| Base technology | Dual flash-based processors with real-time clock, trace diagnostics, programmable languages and character sets |
| Display | White backlit 240 x 64 graphical LCD (5.5 inches x 2.5 inches) |
| LED indicators | 22 red (1 Fire, 1 More Alarms, 20 zonal programmable), 1 green (Power), 13 amber and 7 bi-colour (Fault & System) |
| Number of fire zones | 2000 when networked (400 max across 8 loops) |
| Number of loops | Dedicated 2-8 loop control panel; 2 loop cards as standard |
| Devices per loop | Protocol dependent |
| Loop current | 500mA max per loop |
| On-board sounder circuits | 8 x 1 Amp programmable |
| On-board relays | 4 x 1 Amp 30v AC/DC programmable (10mA, 5v min); expandable to 8 using 2 x MXP-507 |
| Auxiliary supply | 2 x 24v 500mA |
| Programmable inputs | 2 x on-board programmable input |
| Programmable key switch inputs | 16 volt free digital inputs |
| Total output current | 2 x 5A maximum for loop current + sounder outputs + auxiliary supply |
| Mains supply | 200-240v 47-63Hz AC (+10%, -15% tolerance), 1.4A max |
| Charger current | 2 x 2.0A temperature compensated |
| Ethernet port | 10-Base-T, 100-Base-T, providing AdvancedLive connectivity |
| Serial ports | 2 x on-board RS232 for PC, modem, IP or portable printer |
| USB interface | 2 x USB B type for PC communication |
| Programming | On-board keypad or PC running Windows tools |
| Event log | 2 x 5000 event & diagnostic + 500 fire |
| Enclosure / colour | Steel IP30 / RAL7035 |
| Dimensions (H x W x D) | 750 x 450 x 190 mm |
| Cable entry (20mm knockouts) | 30 x top, 6 x top rear, 2 x bottom rear and 3 x bottom |
| Battery capacity | 24v 4Ah min; 24v 45Ah max; 1 x 24V 45Ah internal (max) and 1 x 24V 45Ah external (max) using optional battery enclosure |
| Operating temperature | -5°C to 40°C |
| Humidity (RH) | 95% max |
| Metalwork options | Flushing bezel, battery box, utility enclosure, termination enclosure and rack mount |
| Extra loop card | MXP-567 loop driver card - Nittan, 1 per extra loop |
| Approvals | EN54-2:1997+AC:1999+A1:2006; EN54-4:1997+AC:1999+A1:2002+A2:2006 |
Dimensions
| Dimensions | 750 x 450 x 190 mm (H x W x D) |
|---|
Advanced MxPro 5 Addressable Fire Alarm Panel, 2-8 Loop, Nittan Evolution MX-5802N