About this product
The Advanced TOUCH-10 is a 10 inch touch screen terminal for controlling and viewing a fire alarm network on the standard network type. It suits public areas and sites that want active maps and zone plans. It works with MxPro and AxisEN fire panels and runs on 18-30 V DC.
Key features
- See the whole system at a glance – identifies zones and devices in fire, test, supervisory and fault
- Find it on a plan – active maps and zone plans, set up with the DynamixTools MapApp
- Works with gloves on – a screen designed to work with fireman's glove
- Control from the screen – evacuate, mute, silence, resound and reset
- A second supply can be connected – dual power supply inputs, independently monitored
- Clear status lights – dedicated indicators for Fire, Fault, System Fault, Disabled, Test and Power
- Easier first fix – a 2 part enclosure with slide-in installation
For installers
- Power: supply voltage 18-30 V DC, supply current 300 mA. Dual inputs, and a monitored external input for external PSU faults.
- Mounting: designed to be flush mounted into stud walling. Dimensions H191 x W282 x D80 mm. Surface mounting uses the TOUCH-10-SBB enclosure, ordered separately.
- Cabling: two-core connection to the network, wire gauge up to 2.5 mm2. 20 mm knockouts, 5 top and 5 rear.
- Compatibility: works on Advanced's standard network in this version, with MxPro and AxisEN fire panels.
- Standards: a zone plan display, which Advanced treats as an essential part of BS5839-1.
Frequently asked questions
Which panels does the TOUCH-10 work with?
MxPro and AxisEN fire panels. Do not assume it suits a different range.
Is it for a standard or a fault tolerant network?
Standard. TOUCH-10 is the order code for TouchControl on a standard network, and the fault tolerant network has its own code.
Does it need a separate power supply?
It needs an 18-30 V DC supply at 300 mA. It has dual inputs, plus an input for fault signals from an external PSU.
Can it be surface mounted?
Yes, with the TOUCH-10-SBB enclosure, which is ordered separately. On its own it is designed to flush mount into stud walling.
Does it work with gloves?
Yes. The screen is designed to work with fireman's glove.
Can it show other content when there is no fire?
Yes. It can run presentations, and defaults to normal operation in a fire condition or if the screen is touched.
-
Download
- TOUCH-10 datasheet
Specifications
Dimensions
Specifications
| Brand | Advanced |
|---|---|
| Model | TOUCH-10 |
| Manufacturer Part Number (MPN) | TOUCH-10 |
| Product type | 10 inch, high-resolution touch screen Remote Control Terminal with active maps and zone plans |
| Order code description | TOUCH-10 TouchControl for Standard Network |
| Screen | Designed to work with fireman's glove |
| Compatibility | Compatible with MxPro and AxisEN fire panels |
| Network role | A fire panel and network node in its own right |
| Network connection | Two-core connection to the network |
| Environment | Indoor, dry |
| Supply voltage | 18-30 V DC |
| Supply current | 300 mA |
| Fuse PCB | T250H1.6A |
| PSE fault monitoring | End of line 3300 Ω, ACT 680 Ω |
| Operating temperature | -5°C to +40°C |
| Relative humidity | 95% |
| Wire gauge (max.) | 2.5 mm2 |
| Dimensions | H191 x W282 x D80 mm |
| Knockouts (20mm) | 5 top, 5 rear |
| Wall aperture | 3 mm larger than the back box, nominal 272 x 180 (min 270 x 178, max 274 x 182) |
| Fixing points | 4 x fixing holes in rear of enclosure or 4 x fixing slots in side walls |
| Event log | View 1,000 general and 500 fire event log |
| Status indicators | Fire, Fault, System Fault, Disabled, Test and Power |
Dimensions
| Dimensions | H191 x W282 x D80 mm |
|---|