Apollo Fire Alarm Interface Unit, Intelligent DIN-Rail Input/Output, 1A Relay SA4700-302APO
About this product
The Apollo SA4700-302APO is a fire alarm interface unit that lets an addressable loop monitor volt free contacts and switch a changeover relay. It suits installers linking other equipment to a fire system. It mounts on a 35 mm DIN-rail and works with XP95, Discovery and CoreProtocol communication.
Key features
- Watches outside equipment – supervises one or more normally open volt free contacts on a single pair of cables
- Switches other equipment – changeover relay output contacts rated 1 A at 30 V dc or ac
- A set state if the loop is lost – Failsafe Mode activates the relay on loss of loop or protocol loss, and meets BS 7273-4 requirements
- Tidy in a panel or enclosure – designed for a 35 mm width DIN-Rail, 33 mm height x 102 mm width x 33 mm depth
- Quick to wire – improved design for ease of wiring meaning faster installation
- Status at a glance – separate LEDs for the relay, polling and isolator state, and the input
For installers
- Power: supply voltage 17–35 V dc. Quiescent current 500 µA, max current LEDs on 3.5 mA.
- Mounting: on a 35 mm width DIN-Rail inside an enclosure. Not designed for outdoor use unless mounted in a suitable weatherproof enclosure.
- Cabling: volt free contacts on a single pair of cables, plus changeover relay contacts rated 1 A at 30 V dc or ac. See Installation Guide 39215-160.
- Compatibility: XP95, Discovery and CoreProtocol compatible, fire control panel dependant.
- Standards: EN 54-17, EN 54-18, CPR, LPCB, VdS, BOSEC, SBSC, FG. Failsafe Mode meets BS 7273-4 requirements.
Frequently asked questions
Can the relay switch mains?
No, not directly. The relay output contact rating is 1 A at 30 V dc or ac.
What does failsafe mode do?
It activates the on-board relay without a command from the control panel when the loop or protocol is lost. It is selected with a DIL switch.
Can it be fitted outdoors?
Only in a suitable weatherproof enclosure. On its own the unit is not designed for outdoor use.
Which protocols does it work with?
XP95, Discovery and CoreProtocol, depending on the fire control panel. On XP95 and Discovery it behaves as an XP95 device, and on CoreProtocol as a Soteria device.
Does every panel get all the modes?
No. The nine pre-configured modes are a CoreProtocol enabled systems feature only, so check the panel's documentation.
-
Download
- SA4700-302APO datasheet
Specifications
Dimensions
Specifications
| Brand | Apollo |
|---|---|
| Model | SA4700-302APO |
| Manufacturer Part Number (MPN) | SA4700-302APO |
| Product type | Input/Output Unit |
| Digital communication | XP95, Discovery and CoreProtocol compatible |
| Supply voltage (Vmin–Vmax) | 17–35 V dc |
| Protocol | 5–13 V peak to peak |
| Power-up surge current | 900 µA |
| Quiescent current | 500 µA |
| Max current LEDs on | 3.5 mA |
| Max current LEDs disabled | 500 µA |
| Relay output contact rating | 1 A at 30 V dc or ac |
| Operating temperature | – 40°C to + 70°C |
| Humidity | 0% to 95% RH (no condensation or icing) |
| Vibration, impact and shock | EN 54-17, EN 54-18 |
| Standards and approvals | EN 54-17, EN 54-18, CPR, LPCB, VdS, BOSEC, SBSC, FG |
| Dimensions | 33 mm height x 102 mm width x 33 mm depth |
| Weight | 49 g |
| Isolator | Contains controllable isolator (CoreProtocol enabled systems only) |
| Address range | 1 - 254 (CoreProtocol enabled systems only) |
| Failsafe Mode | Meets BS 7273-4 requirements |
| Input styles | Configurable (CoreProtocol enabled systems only) |
| Device behaviour on XP95/Discovery | XP95 |
| Device behaviour on CoreProtocol | Soteria |
| Operating mode 1 | DIL Switch XP Mode |
| Operating mode 2 | Alarm delays |
| Operating mode 3 | Output and N/O input (can be equivalent for Output only) |
| Operating mode 4 | Output and N/C input |
| Operating mode 5 | Output with Feedback (N/C) |
| Operating mode 6 | FailSafe Output with Feedback (N/C) |
| Operating mode 7 | FailSafe Output without Feedback |
| Operating mode 8 | Momentary Input Activation Sets Output Relay |
| Operating mode 9 | Input Activation Sets Output |
| Status RLY | Continuous Red: Relay Active. Continuous Yellow: Relay Fault |
| Status Poll/ISO | Flashing Green: Polling LED. Continuous Yellow: Isolator LED |
| Status I/P | Continuous Yellow: Input Fault. Continuous Red: Input Active |
Dimensions
| Dimensions | 33 mm height x 102 mm width x 33 mm depth |
|---|
Apollo Fire Alarm Interface Unit, Intelligent DIN-Rail Input/Output, 1A Relay SA4700-302APO