Apollo Series 65 Heat Detector, Class CS, 80°C Application 55000-137APO

£ 13 91
(Incl. VAT) RRP: £16.69
Save £2.78

About this product

The Apollo 55000-137APO is a Series 65 heat detector for conventional fire alarm systems, in class CS standard form. It suits places that are dirty or smoky in normal use, where smoke detectors are unsuitable. Its maximum application temperature is 80°C, with a maximum static response temperature of 100°C.

Key features

  • Goes where smoke detectors can't – for applications where smoke detectors are unsuitable
  • Copes with grime and fumes – suited to environments that are dirty or smoky under normal circumstances
  • For hot spaces – class CS, with a maximum application temperature of 80°C
  • Simple to wire – two wire monitored supply, polarity insensitive
  • Runs on a wide voltage range – 9 V to 33 V
  • Shows when it has operated – red light emitting diode alarm indicator

For installers

  • Power: supply voltage 9 V to 33 V, alarm voltage 6 V to 28 V dc. Holding voltage 6 V, holding current 10 mA.
  • Mounting: 100 mm diameter x 42 mm height, 80 g. Designed to IP54.
  • Cabling: two wire monitored supply, polarity insensitive. L1 IN and L2 are supply in, L1 OUT and L2 supply out, and -R is the remote indicator negative.
  • Compatibility: a Series 65 detector on a conventional circuit. Check the panel's documentation for compatibility.
  • Standards: approvals across the range are CPR, LPCB, VdS, VNIIPO, SBSC, FG and BOMBA, and not all detectors have all approvals.

Frequently asked questions

What does class CS mean on this detector?

It sets the temperatures. Class CS has a maximum application temperature of 80°C and a maximum static response temperature of 100°C.

Is this a rate of rise heat detector?

Rate of rise response belongs to versions with a pair of matched thermistors. This CS version uses a single NTC thermistor network.

How much current does it draw?

Confirm the quiescent and alarm current with Apollo before finalising a circuit design.

Does it have a flashing LED?

No. This part is the CS standard version, with a red light emitting diode as its alarm indicator.

Does the wiring have a polarity?

No. It is a two wire monitored supply and is polarity insensitive.

Which approvals does it hold?

Approvals across the range are CPR, LPCB, VdS, VNIIPO, SBSC, FG and BOMBA, and not all detectors have all approvals. Check this part against your specification.

£ 13 91
RRP: £16.69 Save £2.78
Google Top Quality Store · Rated Exceptional
Ships from United Kingdom
28 days hassle free returns
Secure payment transactions
Price
£13.91 Incl. VAT £16.69
Add a WME Product Care Plan Includes warranty, replacement and repairs backed by WME
Why add a product care plan:
  • Full breakdown support
  • Full replacement if we can't repair your product within 10 days
  • All parts, labour and callouts included if necessary
  • Extended manufacturer warranty with faster turn arounds
  • Excludes accidental & cosmetic damages
By selecting one of these plans you agree to purchase WME Care Plan. Please read the Terms and Important information to ensure WME Care Plan is right for you. Compare prices of extended warranties for electrical goods at www.compareextendedwarranties.co.uk
WME Care
Technical Details
Specifications
Brand
Apollo
Model
55000-137APO
Manufacturer Part Number (MPN)
55000-137APO
Also listed as
55000-137
Product type
Heat Detector CS standard
Class
CS
Maximum application temperature
80°C
Maximum static response temperature
100°C
Sensing
Single NTC thermistor network, voltage output proportional to the external air temperature
Supply wiring
Two wire monitored supply, polarity insensitive
L1 IN and L2
Supply in connections
L1 OUT and L2
Supply out connections
-R
Remote indicator negative connection
Supply voltage
9 V to 33 V
Ripple voltage
2 V peak to peak maximum at 0.1 Hz to 100 kHz
Alarm voltage
6 V to 28 V dc
Alarm indicator
Red light emitting diode
Design alarm load
420 Ω in series with a 2 V drop
Holding voltage
6 V
Holding current
10 mA
Minimum voltage to light alarm indicator
12 V
Remote output
Current sink to the negative line limited to 17 mA
Storage temperature
-30°C to +80°C
Operating temperature
-20°C to +80°C
Humidity
0% to 95% RH, no condensation or icing
Effect of atmospheric pressure
None
IP rating
Designed to IP54
Standards and approvals
CPR, LPCB, VdS, VNIIPO, SBSC, FG, BOMBA. Not all detectors have all approvals
Dimensions
100 mm diameter x 42 mm height
Weight
80 g
Materials
Housing: white flame retardant polycarbonate. Terminals: nickel plated stainless steel
Dimensions
Dimensions
100 mm diameter x 42 mm height

Specifications

Brand Apollo
Model 55000-137APO
Manufacturer Part Number (MPN) 55000-137APO
Also listed as 55000-137
Product type Heat Detector CS standard
Class CS
Maximum application temperature 80°C
Maximum static response temperature 100°C
Sensing Single NTC thermistor network, voltage output proportional to the external air temperature
Supply wiring Two wire monitored supply, polarity insensitive
L1 IN and L2 Supply in connections
L1 OUT and L2 Supply out connections
-R Remote indicator negative connection
Supply voltage 9 V to 33 V
Ripple voltage 2 V peak to peak maximum at 0.1 Hz to 100 kHz
Alarm voltage 6 V to 28 V dc
Alarm indicator Red light emitting diode
Design alarm load 420 Ω in series with a 2 V drop
Holding voltage 6 V
Holding current 10 mA
Minimum voltage to light alarm indicator 12 V
Remote output Current sink to the negative line limited to 17 mA
Storage temperature -30°C to +80°C
Operating temperature -20°C to +80°C
Humidity 0% to 95% RH, no condensation or icing
Effect of atmospheric pressure None
IP rating Designed to IP54
Standards and approvals CPR, LPCB, VdS, VNIIPO, SBSC, FG, BOMBA. Not all detectors have all approvals
Dimensions 100 mm diameter x 42 mm height
Weight 80 g
Materials Housing: white flame retardant polycarbonate. Terminals: nickel plated stainless steel

Dimensions

Dimensions 100 mm diameter x 42 mm height

Apollo 55000-137APO heat detector, side view

Apollo Series 65 Heat Detector, Class CS, 80°C Application 55000-137APO

What this heat detector does

A heat detector reacts to temperature rather than to smoke particles. That makes it useful in rooms where smoke detection would keep false-alarming, such as plant rooms and some kitchens.

This Apollo detector is part of the Series 65 range and is sold here in class CS form. It suits installers and maintainers working on conventional systems in harsh or hot areas.

How it works

  • Thermistor: this is a part whose electrical resistance changes with temperature. CS variants use a single NTC thermistor network, and NTC means the resistance falls as the temperature rises.
  • Alarm signal: the signal processing electronics sit on a printed circuit board inside the moulded case. The output voltage tracks the air outside the detector.
  • Case: the housing is white flame retardant polycarbonate, and the terminals are nickel plated stainless steel.

Where to use it

When choosing between Apollo's heat detector classes, CS is the route where the temperature can increase suddenly.

A heat detector is slower to respond than a smoke detector in most fires, so it is not a straight swap on an escape route. The system designer decides what goes where.

What the figures mean in practice

  • Application temperature: 80°C is the highest normal ambient the class is meant for. It is not the point at which it responds, which is a separate figure.
  • Lighting the indicator: the alarm indicator needs a minimum of 12 V, even though the detector can hold at a lower voltage.
  • Operating range: the detector works from -20°C to +80°C, so it can also suit cold areas within that range.

Installing it

A remote indicator is connected through the -R terminal, a current sink to the negative line limited to 17 mA.

Detector heads are normally sold without a base, so allow a compatible mounting base for each position.

Planning your system

Get the quiescent and alarm figures from Apollo before you finish a circuit design. Check the panel's end-of-line and load limits at the same time.

Use the same maker's range across a circuit where you can, as that keeps the compatibility question simple.

Apollo 55000-137APO heat detector, side view
Apollo Fire

Apollo Series 65 Heat Detector, Class CS, 80°C Application 55000-137APO

£13.91 £16.69

The Apollo 55000-137APO is a Series 65 heat detector for conventional fire alarm systems, in class CS standard form. It suits places that are dirty or smoky in normal use, where smoke detectors are unsuitable. Its maximum application temperature is 80°C, with a maximum static response temperature of 100°C.

Key features

For installers

Frequently asked questions

What does class CS mean on this detector?

It sets the temperatures. Class CS has a maximum application temperature of 80°C and a maximum static response temperature of 100°C.

Is this a rate of rise heat detector?

Rate of rise response belongs to versions with a pair of matched thermistors. This CS version uses a single NTC thermistor network.

How much current does it draw?

Confirm the quiescent and alarm current with Apollo before finalising a circuit design.

Does it have a flashing LED?

No. This part is the CS standard version, with a red light emitting diode as its alarm indicator.

Does the wiring have a polarity?

No. It is a two wire monitored supply and is polarity insensitive.

Which approvals does it hold?

Approvals across the range are CPR, LPCB, VdS, VNIIPO, SBSC, FG and BOMBA, and not all detectors have all approvals. Check this part against your specification.