Apollo Orbis Optical Smoke Detector, Two Wire, IP44 ORB-OP-12001-APO

£ 16 27
(Incl. VAT) RRP: £19.52
Save £3.25

About this product

The Apollo ORB-OP-12001-APO is an Orbis optical smoke detector for conventional fire alarm systems, recommended by Apollo as a general purpose smoke detector for early warning of fires in most areas. It suits installers wanting fewer false alarms. It runs on a two wire supply from 8.5 V dc to 33 V dc.

Key features

  • Better on dark smoke – improved sensitivity to black smoke
  • Copes as it ages – compensation for build-up of dirt
  • Fewer nuisance alarms – extra confirmation of smoke before an alarm signal is given
  • Easy to see from below – integral indicator with 360º visibility
  • Quick to check – FasTest takes just four seconds to test that it is functioning correctly
  • Shows wiring faults early – StartUp confirms that the detectors are wired in the correct polarity

For installers

  • Power: 8.5 V dc to 33 V dc. Average quiescent current at 24 V is 95 µA, and alarm current is 40 mA at 24V.
  • Mounting: 97 mm diameter x 31 mm height, 75 g. IP44.
  • Cabling: two wire supply, polarity sensitive. Remote output LED (-) is 1.2 kΩ connected to negative supply.
  • Compatibility: a conventional detector. Check your panel's documentation for compatibility, and allow a suitable base.
  • Standards: EN54-7, with CPR, LPCB, VdS, BOSEC, SBSC and FG for this part number.

Frequently asked questions

Does the polarity matter when wiring it?

Yes. It is polarity sensitive, and StartUp flashes the red LED once per second to confirm that the wiring is in the correct polarity.

Is the LED flashing in normal use?

No. This part has no flashing LED as standard. There is a separate flashing LED version, ORB-OP-12003-APO.

How is a dirty detector shown?

By the yellow LED. DirtAlert shows that the drift compensation limit has been reached, flashing once per second in StartUp.

Can it be used on an escape route?

Optical detectors are regarded as particularly suitable for smouldering fires and escape routes, but the system design for the building decides each position.

Which temperatures can it work in?

From -40ºC to +70ºC, with humidity from 0% to 98% RH and no condensation or icing.

Does it come with a base?

As a rule, detector heads are sold without one, so check before ordering.

£ 16 27
RRP: £19.52 Save £3.25
Google Top Quality Store · Rated Exceptional
Ships from United Kingdom
28 days hassle free returns
Secure payment transactions
Price
£16.27 Incl. VAT £19.52
Add a WME Product Care Plan Includes warranty, replacement and repairs backed by WME
Why add a product care plan:
  • Full breakdown support
  • Full replacement if we can't repair your product within 10 days
  • All parts, labour and callouts included if necessary
  • Extended manufacturer warranty with faster turn arounds
  • Excludes accidental & cosmetic damages
By selecting one of these plans you agree to purchase WME Care Plan. Please read the Terms and Important information to ensure WME Care Plan is right for you. Compare prices of extended warranties for electrical goods at www.compareextendedwarranties.co.uk
WME Care
Technical Details
Specifications
Brand
Apollo
Model
ORB-OP-12001-APO
Manufacturer Part Number (MPN)
ORB-OP-12001-APO
Product
Optical Smoke Detector
Detection principle
Photo-electric detection of light scattered by smoke particles over a wide range of angles
Sampling frequency
Once every four seconds
Operating voltage
8.5 V dc to 33 V dc
Supply wiring
Two wire supply, polarity sensitive
Maximum polarity reversal
200 ms
Power up time
< 20 seconds
Minimum detector active voltage
6 V
Average quiescent current at 24 V
95 µA
Alarm current
12 V: 20 mA; 24V: 40 mA
Alarm load
600 Ω
Holding voltage
5 V - 33 V
Minimum holding current
8 mA
Minimum voltage to light alarm LED
5 V
Alarm reset voltage
< 1 V
Alarm reset time
One second
Alarm indicator
Integral indicator with 360º visibility
Remote output LED (-)
1.2 kΩ connected to negative supply
Operating and storage temperature
-40ºC to +70ºC
Humidity
0% to 98% RH, no condensation or icing
Effect of atmospheric pressure on optical sensor
None
Effect of wind speed
None
IP rating
IP44
Standards
EN54-7
Approvals for this part
CPR, LPCB, VdS, BOSEC, SBSC, FG
Dimensions
97 mm diameter x 31 mm height
Weight
75 g
Materials
Housing: white flame retardant polycarbonate. Terminals: tin plated stainless steel
Dimensions
Dimensions
97 mm diameter x 31 mm height

Specifications

Brand Apollo
Model ORB-OP-12001-APO
Manufacturer Part Number (MPN) ORB-OP-12001-APO
Product Optical Smoke Detector
Detection principle Photo-electric detection of light scattered by smoke particles over a wide range of angles
Sampling frequency Once every four seconds
Operating voltage 8.5 V dc to 33 V dc
Supply wiring Two wire supply, polarity sensitive
Maximum polarity reversal 200 ms
Power up time < 20 seconds
Minimum detector active voltage 6 V
Average quiescent current at 24 V 95 µA
Alarm current 12 V: 20 mA; 24V: 40 mA
Alarm load 600 Ω
Holding voltage 5 V - 33 V
Minimum holding current 8 mA
Minimum voltage to light alarm LED 5 V
Alarm reset voltage < 1 V
Alarm reset time One second
Alarm indicator Integral indicator with 360º visibility
Remote output LED (-) 1.2 kΩ connected to negative supply
Operating and storage temperature -40ºC to +70ºC
Humidity 0% to 98% RH, no condensation or icing
Effect of atmospheric pressure on optical sensor None
Effect of wind speed None
IP rating IP44
Standards EN54-7
Approvals for this part CPR, LPCB, VdS, BOSEC, SBSC, FG
Dimensions 97 mm diameter x 31 mm height
Weight 75 g
Materials Housing: white flame retardant polycarbonate. Terminals: tin plated stainless steel

Dimensions

Dimensions 97 mm diameter x 31 mm height

Apollo ORB-OP-12001-APO optical smoke detector, angled view

Apollo Orbis Optical Smoke Detector, Two Wire, IP44 ORB-OP-12001-APO

Overview

An optical detector looks for smoke by using light, so it responds to smoke rather than to heat. This Apollo detector is one of the Orbis range and comes in a white flame retardant polycarbonate housing.

Its performance is good with black as well as with white smoke, whereas traditional optical detectors perform far better in white smoke than in black.

How it works

  • Light scatter: smoke entering the chamber scatters light onto a sensor. The chamber measures back-scattered light as well as the more usual forward-scattered light.
  • Sampling: it samples once every four seconds, and algorithms then decide when it should change to the alarm state.
  • Drift compensation: dust slowly changes what a sensor reads, so the detector allows for that up to a limit. DirtAlert then shows that the limit has been reached.

Where to use it

Its algorithms are designed to reduce alarms from smoke from smoking materials.

Steam, cooking fumes and heavy dust can still set off an optical detector, so a heat detector is often the better choice in kitchens and plant rooms.

Its operating range of -40ºC to +70ºC is wide, while IP44 gives only moderate protection against dust and splashes.

What the figures mean in practice

  • Current at rest: the 95 µA figure at 24 V is what each detector adds to a circuit when idle. Compare the total with the panel's allowance.
  • Alarm voltage: the red alarm LED lights from a minimum of 5 V, and the holding voltage runs from 5 V to 33 V.
  • Reset: the supply has to fall below 1 V for about one second for the alarm to reset.

Installing it

Allow time after power up, which is < 20 seconds. Polarity reversal must not last more than 200 ms, which is why the StartUp check is worth watching on first power up.

As a rule, detector heads are sold without a base, so allow a suitable mounting base for each position.

Planning your system

A conventional system wires its devices in zones, so the panel names a zone and not a single head. The fire alarm system guide compares that with addressable systems.

For loop-based work, the other Apollo smoke detectors cover addressable and wireless systems.

Standards and ratings explained

EN54-7 is the standard for point smoke detectors. CPR refers to the Construction Products Regulation, and the detector complies with its essential requirements.

SensAlert indicates that the sensor is not operating correctly, so treat that signal as a reason to replace or service the head.

Apollo ORB-OP-12001-APO optical smoke detector, angled view
Apollo Fire

Apollo Orbis Optical Smoke Detector, Two Wire, IP44 ORB-OP-12001-APO

£16.27 £19.52

The Apollo ORB-OP-12001-APO is an Orbis optical smoke detector for conventional fire alarm systems, recommended by Apollo as a general purpose smoke detector for early warning of fires in most areas. It suits installers wanting fewer false alarms. It runs on a two wire supply from 8.5 V dc to 33 V dc.

Key features

For installers

Frequently asked questions

Does the polarity matter when wiring it?

Yes. It is polarity sensitive, and StartUp flashes the red LED once per second to confirm that the wiring is in the correct polarity.

Is the LED flashing in normal use?

No. This part has no flashing LED as standard. There is a separate flashing LED version, ORB-OP-12003-APO.

How is a dirty detector shown?

By the yellow LED. DirtAlert shows that the drift compensation limit has been reached, flashing once per second in StartUp.

Can it be used on an escape route?

Optical detectors are regarded as particularly suitable for smouldering fires and escape routes, but the system design for the building decides each position.

Which temperatures can it work in?

From -40ºC to +70ºC, with humidity from 0% to 98% RH and no condensation or icing.

Does it come with a base?

As a rule, detector heads are sold without one, so check before ordering.