Fike Twinflex Soundpoint Fire Alarm Sounder, Red, 85dB(A), 2-Wire 313-0021

£ 28 62
(Incl. VAT) RRP: £34.34
Save £5.72

About this product

The Fike 313-0021 is a red Twinflex Soundpoint fire alarm sounder for 2-wire Twinflex zones. It is powered from the zone itself, so it can share the wiring with Multipoint detectors. It suits installers extending or fitting out a system, with up to 85+ dB(A) on its high setting.

Key features

  • No separate power run – a 2-wire zone-powered sounder
  • Shares a zone with detectors – may be installed on the same zone as the Multipoint detector/sounder
  • Two volume settings – 85+ dB(A) on high and 65+ dB(A) on low, @ 1m anechoic, Dual Tone
  • Choice of sound – Dual Tone UK Evacuate, Slow Whoop Up or Dual Tone French Warble, set by DIL switch
  • End of line built in – switch number 1 turns on the end of line signal, with no resistor needed on the last device
  • Surface or flush fixing – a surface back box, or flush with the adaptor plate
  • Tested as a fire alarm sounder – EN54-3: 2001 +A1: 2002 +A2: 2006

For installers

  • Power: 25.5 to 35V DC from a mains powered panel, 20 to 26V DC from a battery powered panel. Alarm current typically 14.5 mA on high.
  • Mounting: 89 mm wide and 89 mm high. Surface depth 62 mm; flush it protrudes 34 mm, on a standard single gang flush back box with a minimum internal depth of 47mm.
  • Cabling: zone +VE (red), zone -VE (blue) and screen (E). Connect E only to the zone cable screen, not the building earth.
  • Compatibility: the Twinflex 2-wire range. Loading on high is 2.5 SLU on a V3 panel and 14.5 DLU on a Pro panel.
  • Standards: EN54-3: 2001 +A1: 2002 +A2: 2006. Rated IP 21C.

Frequently asked questions

Does the Soundpoint need its own power supply?

No. It is a 2-wire zone-powered sounder, so it runs from the Twinflex zone.

How loud is it?

85+ dB(A) on high and 65+ dB(A) on low, measured @ 1m anechoic, Dual Tone.

Can it be flush mounted?

Yes, with the adaptor plate and a standard single gang flush back box. That box needs a minimum internal depth of 47mm.

Should an end of line resistor be fitted?

No. Do not use a resistor or capacitor as the end of line. On the last device, set switch number 1 to ON instead.

Can the E terminal go to the building earth?

No. It should only be connected to the zone cable screen. The screen is connected to earth at the panel end only.

Can it be used outdoors?

It is not a good fit for wet or exposed positions. It is rated IP 21C, and the surface back box is for a flat vertical surface.

£ 28 62
RRP: £34.34 Save £5.72
Google Top Quality Store · Rated Exceptional
Ships from United Kingdom
28 days hassle free returns
Secure payment transactions
Price
£28.62 Incl. VAT £34.34
Add a WME Product Care Plan Includes warranty, replacement and repairs backed by WME
Why add a product care plan:
  • Full breakdown support
  • Full replacement if we can't repair your product within 10 days
  • All parts, labour and callouts included if necessary
  • Extended manufacturer warranty with faster turn arounds
  • Excludes accidental & cosmetic damages
By selecting one of these plans you agree to purchase WME Care Plan. Please read the Terms and Important information to ensure WME Care Plan is right for you. Compare prices of extended warranties for electrical goods at www.compareextendedwarranties.co.uk
WME Care
Technical Details
Specifications
Brand
Fike
Model
313-0021
Manufacturer Part Number (MPN)
313-0021
Product type
2-wire zone-powered sounder
Range
Twinflex Soundpoint
Colour
Red
Compatibility
Twinflex 2-wire range of fire alarm equipment
Width
89 mm
Height
89 mm
Flush depth protruding
34 mm
Surface depth
62 mm
Flush back box
Standard single gang, minimum internal depth 47mm
Surface back box cable entry
20mm hole at the rear; may be drilled
Operating temperature
-10°C to +50°C
Voltage, mains powered panel
25.5 to 35V DC
Voltage, battery powered panel
20 to 26V DC
Quiescent current (typical)
185 uA
End of line ON, in addition to quiescent (typical)
175 uA
Alarm sounding, sounder high (typical)
14.5 mA
Alarm sounding, sounder low (typical)
12.6 mA
Max loading units per zone
V3 panel 27 SLU; Pro panel 160 DLU
Loading, sounder high
V3 panel 2.5 SLU; Pro panel 14.5 DLU
Loading, sounder low
V3 panel 2.0 SLU; Pro panel 13.0 DLU
Volume, sounder high
85+ dB(A) @ 1m anechoic, Dual Tone
Volume, sounder low
65+ dB(A) @ 1m anechoic, Dual Tone
Dual Tone UK Evacuate
800 & 970 Hz
Slow Whoop Up
500 to 1200 Hz sweep up
Dual Tone French Warble
440 & 550 HZ
Flammability
UL94-V2
IP rating
IP 21C
Standard
EN54-3: 2001 +A1: 2002 +A2: 2006
Declaration of Performance
DoP-313-0021
Dimensions
Dimensions
89 mm wide x 89 mm high; surface depth 62 mm

Specifications

Brand Fike
Model 313-0021
Manufacturer Part Number (MPN) 313-0021
Product type 2-wire zone-powered sounder
Range Twinflex Soundpoint
Colour Red
Compatibility Twinflex 2-wire range of fire alarm equipment
Width 89 mm
Height 89 mm
Flush depth protruding 34 mm
Surface depth 62 mm
Flush back box Standard single gang, minimum internal depth 47mm
Surface back box cable entry 20mm hole at the rear; may be drilled
Operating temperature -10°C to +50°C
Voltage, mains powered panel 25.5 to 35V DC
Voltage, battery powered panel 20 to 26V DC
Quiescent current (typical) 185 uA
End of line ON, in addition to quiescent (typical) 175 uA
Alarm sounding, sounder high (typical) 14.5 mA
Alarm sounding, sounder low (typical) 12.6 mA
Max loading units per zone V3 panel 27 SLU; Pro panel 160 DLU
Loading, sounder high V3 panel 2.5 SLU; Pro panel 14.5 DLU
Loading, sounder low V3 panel 2.0 SLU; Pro panel 13.0 DLU
Volume, sounder high 85+ dB(A) @ 1m anechoic, Dual Tone
Volume, sounder low 65+ dB(A) @ 1m anechoic, Dual Tone
Dual Tone UK Evacuate 800 & 970 Hz
Slow Whoop Up 500 to 1200 Hz sweep up
Dual Tone French Warble 440 & 550 HZ
Flammability UL94-V2
IP rating IP 21C
Standard EN54-3: 2001 +A1: 2002 +A2: 2006
Declaration of Performance DoP-313-0021

Dimensions

Dimensions 89 mm wide x 89 mm high; surface depth 62 mm

Fike 313-0021 Twinflex Soundpoint fire alarm sounder, front angled view

Fike Twinflex Soundpoint Fire Alarm Sounder, Red, 85dB(A), 2-Wire 313-0021

What this sounder does

A sounder is the part of a fire alarm that people hear. This Fike unit gives audible indication once the system enters an alarm condition.

It takes both its power and its signal from the Twinflex zone. There is no separate sounder circuit to run, which is the main point of a 2-wire system.

How it works

  • DIL switches: four small on/off switches set the end of line, the level and the pattern. They can be changed with the device powered or with the system powered down.
  • Sound off setting: the pattern settings also include a Sound OFF position, so check the switches before handing over.
  • Mixed zones: Soundpoints can sit alongside Multipoint detectors on one zone. Each device type has its own instructions for terminal details.

Where to use it

It suits dry indoor areas where a wall sounder is wanted on a Twinflex zone. Surface mounting needs a flat vertical surface.

UK buildings normally use one agreed alarm sound throughout. Choose the pattern with whoever holds the fire strategy.

What the figures mean in practice

  • Volume test: anechoic means a room with no echoes, so real rooms will measure differently. Check audibility on site once it is commissioned.
  • Loading units: these show how much of a zone's capacity one sounder uses. Add up every device against the maximum for your panel type: 27 SLU on V3, 160 DLU on Pro.
  • End of line current: the extra 175 uA only applies on the device with its end of line signal switched on.
  • Voltage ranges: the range differs with the panel's power source, so check which applies when planning a long cable run.

Installing it

  • First fix: use at least two of the four holes in the surface back box. Zone cabling may be connected to its terminals.
  • Test before fitting the front: all high voltage testing comes first, otherwise the electronics will be damaged.
  • Second fix: connect the wires by colour, hook the top into the back box, push it gently home, then tighten the single fixing screw.
  • Screen: keep it continuous along the zone, which protects against data corruption from interference.
  • Who does it: commissioning should only be carried out by competent persons.

Planning your system

It needs a Twinflex panel, because it is made for the Twinflex range. A compatible Fike control panel and a detector on the same zone make up the core of the job.

For flush fixing, allow for the adaptor plate and the 47mm depth of back box. Fike's spacing advice points to BS5839 Pt1, so work to the current edition.

The guide to a commercial fire alarm system covers categories and zones, which come before choosing devices.

Standards and ratings explained

  • EN54-3: the European standard for fire alarm sounders.
  • IP 21C: the 2 means protection against fingers and objects over 12.5mm, and the 1 means protection against vertically dripping water. The C is an extra rating for access by tools.
  • UL94-V2: a test of how plastic behaves in flame, and V2 is one grade on that scale.
Fike 313-0021 Twinflex Soundpoint fire alarm sounder, front angled view
Fike

Fike Twinflex Soundpoint Fire Alarm Sounder, Red, 85dB(A), 2-Wire 313-0021

£28.62 £34.34

The Fike 313-0021 is a red Twinflex Soundpoint fire alarm sounder for 2-wire Twinflex zones. It is powered from the zone itself, so it can share the wiring with Multipoint detectors. It suits installers extending or fitting out a system, with up to 85+ dB(A) on its high setting.

Key features

For installers

Frequently asked questions

Does the Soundpoint need its own power supply?

No. It is a 2-wire zone-powered sounder, so it runs from the Twinflex zone.

How loud is it?

85+ dB(A) on high and 65+ dB(A) on low, measured @ 1m anechoic, Dual Tone.

Can it be flush mounted?

Yes, with the adaptor plate and a standard single gang flush back box. That box needs a minimum internal depth of 47mm.

Should an end of line resistor be fitted?

No. Do not use a resistor or capacitor as the end of line. On the last device, set switch number 1 to ON instead.

Can the E terminal go to the building earth?

No. It should only be connected to the zone cable screen. The screen is connected to earth at the panel end only.

Can it be used outdoors?

It is not a good fit for wet or exposed positions. It is rated IP 21C, and the surface back box is for a flat vertical surface.