Hochiki Conventional Rate of Rise Heat Detector, 90 °C Fixed Element, White DCD-CE3(WHT)
About this product
The Hochiki DCD-CE3(WHT) is a conventional combined rate of rise and fixed temperature heat detector in white. It is a rate of rise heat detector with a 90 °C fixed temperature element, using a thermistor and linearising circuit. A third terminal provides remote indicator output, and it works from 9.5 – 30 V dc.
Key features
- Electronic linear heat detection – a thermistor and linearising circuit give an accurate linear response
- Two ways to detect – rate of rise heat detection with a 90 °C fixed temperature element
- Easy to see in alarm – twin fire LEDs allow 360° viewing
- Remote indicator output – 20 mA (max) / 9.5-14 mA (typ) drive
- Wide voltage range – 9.5 ~ 30 V dc
- Full range of mounting bases – YBN-R6, YBN-R/6SK and YBO-R/6 bases
- Approved by LPCB & VdS – Class C & CR to EN54:2000
For installers
- Power: operating voltage 9.5 – 30 V dc; maximum current in alarm 40 mA.
- Mounting: fits a compatible base with 48 ~ 74 mm fixing centres. 100 mm diameter, 38 mm high, 76 g.
- Compatibility: compatible bases YBN-R6, YBN-R/6SK, YBO-R/6R, YBO-R/6RS, YBO-R/6RN and YBO-R/6PA, supported on the majority of conventional systems.
- Cabling: a third terminal gives the remote indicator output, 20 mA (max) / 9.5-14 mA (typ).
- Standards: approvals to (EN54:2000) Class C & CR, LPCB and VdS; IP63.
Frequently asked questions
What temperature does it alarm at?
It is a rate of rise heat detector, and its fixed temperature element also alarms at 90 °C.
Can it detect smoke?
No. The DCD range is used to detect conditions and changes in temperature and cannot detect smoke.
Which bases does it fit?
Compatible bases are YBN-R6, YBN-R/6SK, YBO-R/6R, YBO-R/6RS, YBO-R/6RN and YBO-R/6PA.
What voltage does it need?
9.5 – 30 V dc.
What colour is it?
White. The same detector is also sold in ivory under the code DCD-CE3.
Can it be fitted outdoors?
No. These detectors are designed for indoor use only.
-
Download
- DCD-CE3(WHT) datasheet
Specifications
Dimensions
Specifications
| Brand | Hochiki |
|---|---|
| Model | DCD-CE3(WHT) |
| Manufacturer Part Number (MPN) | DCD-CE3(WHT) |
| Type | Conventional combined rate of rise and fixed temperature heat detector |
| Fixed temperature | 90 °C |
| Ordering code | DCD-CE3(WHT) |
| Colour | White |
| Case material | Polycarbonate |
| Operating voltage | 9.5 – 30 V dc |
| Maximum current in alarm | 40 mA |
| Remote indicator drive | 20 mA (max) / 9.5-14 mA (typ) |
| Operating temperature range | -10 °C to +50 °C |
| Storage temperature range | -30 °C to +70 °C |
| Maximum humidity | 95% RH, non condensing (at 40 °C) |
| Ingress protection rating | IP63 |
| Weight | 76 g |
| Dimensions | 100 mm diameter x 38 mm height |
| Compatible bases | YBN-R6, YBN-R/6SK, YBO-R/6R, YBO-R/6RS, YBO-R/6RN, YBO-R/6PA |
| Base fixing centres | 48 ~ 74 mm |
| Indicators | Twin fire LEDs, 360° viewing |
| Approvals | EN54:2000 Class C & CR; LPCB; VdS (G204045) |
Dimensions
| Dimensions | 100 mm diameter x 38 mm height |
|---|