Hochiki Plant Control Module, 4 Relay Outputs, 4 Inputs, Loop Powered CHQ-PCM(SCI)
About this product
The Hochiki CHQ-PCM(SCI) is a plant control module for fire alarm panels using ESP, with four change-over relay outputs and four monitored inputs. It suits installers shutting down plant or controlling dampers from the loop. It is loop powered, has a single loop address and includes a short-circuit isolator.
Key features
- Four outputs to control plant – 4 change-over relay outputs, each driven separately by the panel
- Either contact state to hand – N/O and N/C volt free contacts
- Local fire and fault signals back to the panel – four inputs, fully monitored for open and short circuit
- No separate power supply for the module – loop powered, with single loop address
- Helps limit a loop fault – integral short-circuit isolator
- Status at a glance – green LED flashes when polled, amber LED when a short-circuit fault is detected
For installers
- Power: loop powered, 17 - 41 VDC. Quiescent current 300 μA, 22 mA ± 20 % whilst polling.
- Mounting: Smart-Fix back plate with lid, L157 x W127 x H35, 332 g. Fixings are not supplied.
- Cabling: relay contacts 30 VDC max, 1 A (resistive load). Input E.O.L resistor 10 kΩ, ±5%, 0.25 W.
- Compatibility: digital communication using ESP. Fire alarm control panel compatibility is required, so check your panel's documentation.
- Standards: LPCB (EN 54-17:2005, EN 54-18:2005).
In the box
- Smart-Fix CHQ Module (back plate including the PCB)
- CHQ-LID transparent module lid, with four screws and acrylic retaining washers
- All end of line and operational resistors
Frequently asked questions
What can a plant control module switch?
Devices such as dampers, or plant and equipment shutdown, under the control of the fire alarm panel. The relay contacts are rated 30 VDC max, 1 A (resistive load).
Can it switch mains directly?
No. The rating is 30 VDC max, 1 A (resistive load), so higher loads need a suitable interposing relay chosen by your installer.
What state are the relays in at power-up?
Treat them as unknown. The state of the relay contacts will be indeterminate until the unit is powered.
How is the loop address set?
With the first 7 switches of the 8-bit DIL switch. Switch 8 is not used and stays off.
Can input monitoring be turned off?
Yes, in pairs, using a two-way DIL switch. The unit then ignores open or short-circuit conditions.
Specifications
Dimensions
Specifications
| Brand | Hochiki |
|---|---|
| Model | CHQ-PCM(SCI) |
| Manufacturer Part Number (MPN) | CHQ-PCM(SCI) |
| Product type | Analogue Plant Control Module |
| Transmission method | Digital communication using ESP |
| Operating voltage | 17 - 41 VDC |
| Quiescent current | 300 μA |
| Current consumption whilst polling | 22 mA ± 20 % |
| Relay contact rating | 30 VDC max, 1 A (resistive load) |
| Input E.O.L resistor | 10 kΩ, ±5%, 0.25 W |
| Input threshold level | ON=470 Ω, Short cct <50 Ω, Open cct >100 KΩ |
| Maximum rated current | 1 A (switch closed) |
| Leakage current | 3 mA (switch open) |
| Weight with lid | 332 g |
| Dimensions with lid | L157 x W127 x H35 |
| Weight with lid and CHQ-BACKBOX | 567 g |
| Height with lid and CHQ-BACKBOX | H79 |
| Colour and enclosure material | CHQ Module white ABS |
| Approvals | LPCB (EN 54-17:2005, EN 54-18:2005) |
Dimensions
| Dimensions | L157 x W127 x H35 with lid |
|---|
Hochiki Plant Control Module, 4 Relay Outputs, 4 Inputs, Loop Powered CHQ-PCM(SCI)