Morley-IAS MI-DCMOE Addressable Single Output Module with Short-Circuit Isolator

£ 80 65
(Incl. VAT) RRP: £96.78
Save £16.13

About this product

The Morley-IAS MI-DCMOE is an addressable output module for controlling auxiliary devices such as fire shutters or sounders from the fire alarm loop. It suits installers adding cause-and-effect outputs to a compatible analogue addressable system. It has one relay rated 30V DC, 2A resistive, and a built-in loop isolator.

Key features

  • Controls plant from the loop – one relay output for shutters, sounders and other auxiliary devices
  • Keeps the loop running on a short – built-in short circuit monitoring and isolators
  • Status at a glance – tri-colour LED, green when the relay is energised
  • Choose the wiring – supervised or non-supervised operation
  • Watches its own supply – supervised mode flags a supply below 7V
  • Two mounting options – M200E-SMB surface box or 35 mm DIN rail

For installers

  • Power: 15 to 32VDC from the loop (min 16.5VDC for LED operation); 160 µA maximum standby. External supply for supervised mode: max. 32V DC, min. 7V DC.
  • Cabling: plug in terminals for conductors up to 2.5 mm². For output supervision, fit the link across terminals 6 and 7; the load must be polarised.
  • Mounting: M200E-SMB surface box, 132 mm (H) x 137 mm (W) x 40 mm (D), or a 35 mm x 7.5 mm Top Hat DIN rail inside a panel or enclosure.
  • Compatibility: only for panels using compatible proprietary analogue addressable protocols. Check the panel's documentation before ordering.
  • Standards: EN54-17: 2005 and EN54-18: 2005; declaration of performance DOP-IOD080.

Frequently asked questions

What can the MI-DCMOE switch?

Auxiliary devices such as fire shutters or sounders. The relay contacts are rated 30V DC, 2A resistive load.

Can it switch mains voltage directly?

No. Its relay is rated 30V DC, 2A resistive, so larger or mains loads need a suitably rated interposing relay.

Does it have a short-circuit isolator?

Yes. It has short circuit monitoring and an isolator on the loop, which can be wired out on high current loaded loops.

How is the address set?

With rotary decade address switches, turned with a screwdriver. The number of usable addresses depends on the panel.

Which panels does it work with?

Panels using a compatible proprietary analogue addressable protocol. Check the panel's documentation before fitting.

£ 80 65
RRP: £96.78 Save £16.13
Google Top Quality Store · Rated Exceptional
Ships from United Kingdom
28 days hassle free returns
Secure payment transactions
Price
£80.65 Incl. VAT £96.78
Add a WME Product Care Plan Includes warranty, replacement and repairs backed by WME
Why add a product care plan:
  • Full breakdown support
  • Full replacement if we can't repair your product within 10 days
  • All parts, labour and callouts included if necessary
  • Extended manufacturer warranty with faster turn arounds
  • Excludes accidental & cosmetic damages
By selecting one of these plans you agree to purchase WME Care Plan. Please read the Terms and Important information to ensure WME Care Plan is right for you. Compare prices of extended warranties for electrical goods at www.compareextendedwarranties.co.uk
WME Care
Technical Details
Specifications
Brand
Morley-IAS
Model
MI-DCMOE
Manufacturer Part Number (MPN)
MI-DCMOE
Product
Addressable single output module
Operating voltage range
15 to 32VDC (min 16.5VDC for LED operation)
Maximum standby current
160 µA (no communication)
LED current
Red 1.5 mA; yellow 5.5 mA
Relay contact rating
30V DC, 2A resistive load
Output modes
Supervised or non-supervised
External supply (supervised mode)
Max. 32V DC, min. 7V DC
Status LED
Single tri-colour
Short-circuit isolator
Built in; can be wired out
Addressing
Rotary decade address switches
Terminals
Plug in, conductors up to 2.5 mm²
Mounting
M200E-SMB surface box or 35 mm x 7.5 mm Top Hat DIN rail
Surface box dimensions
132 mm (H) x 137 mm (W) x 40 mm (D)
Humidity
5% to 95% relative humidity (non-condensing)
Standards
EN54-17: 2005, EN54-18: 2005
Declaration of performance
DOP-IOD080

Specifications

Brand Morley-IAS
Model MI-DCMOE
Manufacturer Part Number (MPN) MI-DCMOE
Product Addressable single output module
Operating voltage range 15 to 32VDC (min 16.5VDC for LED operation)
Maximum standby current 160 µA (no communication)
LED current Red 1.5 mA; yellow 5.5 mA
Relay contact rating 30V DC, 2A resistive load
Output modes Supervised or non-supervised
External supply (supervised mode) Max. 32V DC, min. 7V DC
Status LED Single tri-colour
Short-circuit isolator Built in; can be wired out
Addressing Rotary decade address switches
Terminals Plug in, conductors up to 2.5 mm²
Mounting M200E-SMB surface box or 35 mm x 7.5 mm Top Hat DIN rail
Surface box dimensions 132 mm (H) x 137 mm (W) x 40 mm (D)
Humidity 5% to 95% relative humidity (non-condensing)
Standards EN54-17: 2005, EN54-18: 2005
Declaration of performance DOP-IOD080

Morley-IAS MI-DCMOE addressable output module, front view

Morley-IAS MI-DCMOE Addressable Single Output Module with Short-Circuit Isolator

Overview

An output module lets an addressable fire panel switch something else when a fire is detected. This Morley-IAS module has one relay output and sits on the loop at its own address.

It is part of a family of microprocessor controlled interface devices that monitor or control auxiliary equipment.

How it works

  • Relay output: the panel commands the relay to its energised state, and the LED can show continuous green while it is.
  • Supervised mode: with a polarised load and the link fitted, the module checks the output circuit and its external supply, and flags a fault if the supply falls below 7V.
  • Loop isolation: the built-in isolator separates a short on the loop so the rest keeps working.

Where to use it

Use it where the fire alarm has to operate shutters, sounder circuits or other equipment through a relay. Keep it in a dry indoor space or inside a panel or enclosure.

What the figures mean in practice

  • 30V DC, 2A resistive: the contacts suit low-voltage DC loads. For anything larger, have the module drive an interposing relay that is rated for the load.
  • Inductive loads: coils and motors can cause switching surges that damage the contacts, so fit a transient voltage suppressor such as 1N6284CA across the load.

Installing it

Disconnect loop power first, and handle the module as an electrostatic sensitive device. Set the address on the rotary switches before fitting.

On loops with high current loads such as sounders, the isolator can be wired out by taking the loop out positive to terminal 5 instead of terminal 2.

Planning your system

Cause and effect, loop loading and battery standby are part of the system design; the fire alarm system guide explains how they fit together. For mains loads, add a suitable control relay.

A supervised output needs an external supply, such as one of the fire alarm power supplies. Other fire panel modules cover inputs and combined inputs and outputs, and more Morley-IAS equipment completes the system.

Standards and ratings explained

  • EN54-17: the standard for short-circuit isolators in fire detection systems.
  • EN54-18: the standard for input and output devices, such as this module.
Morley-IAS MI-DCMOE addressable output module, front view
Morley-IAS

Morley-IAS MI-DCMOE Addressable Single Output Module with Short-Circuit Isolator

£80.65 £96.78

The Morley-IAS MI-DCMOE is an addressable output module for controlling auxiliary devices such as fire shutters or sounders from the fire alarm loop. It suits installers adding cause-and-effect outputs to a compatible analogue addressable system. It has one relay rated 30V DC, 2A resistive, and a built-in loop isolator.

Key features

For installers

Frequently asked questions

What can the MI-DCMOE switch?

Auxiliary devices such as fire shutters or sounders. The relay contacts are rated 30V DC, 2A resistive load.

Can it switch mains voltage directly?

No. Its relay is rated 30V DC, 2A resistive, so larger or mains loads need a suitably rated interposing relay.

Does it have a short-circuit isolator?

Yes. It has short circuit monitoring and an isolator on the loop, which can be wired out on high current loaded loops.

How is the address set?

With rotary decade address switches, turned with a screwdriver. The number of usable addresses depends on the panel.

Which panels does it work with?

Panels using a compatible proprietary analogue addressable protocol. Check the panel's documentation before fitting.