Notifier System Sensor Smoke Detector Base, Analogue, Pure White, 200 Series B501AP

£ 3 95
(Incl. VAT) RRP: £4.74
Save £0.79

About this product

The Notifier System Sensor B501AP is a pure white analogue sensor base for System Sensor 200 Series detectors. It suits installers working on intelligent fire alarm systems. It has SEMS screw connections, takes both isolated and non-isolated detectors, and carries an address identification label.

Key features

  • Made for 200 Series detectors – a mounting base designed for use with System Sensor 200 Series detectors
  • Simple wiring – SEMS screws (a screw with a captive washer) provide easy wiring connection
  • Takes both detector types – for isolated and non-isolated detectors
  • Detector goes on quickly – quick and secure detector plug-in
  • Discourages tampering – break off a plastic tab, and the detector cannot be removed without a suitable tool
  • Easy to identify on site – can be labelled with a break-off address tag

For installers

  • Mounting: four-inch flangeless mounting base. Multiple accessory options provide mounting flexibility.
  • Cabling: SEMS screw connections, with support for 24 to 12 AWG.
  • Compatibility: System Sensor 200 Series detectors, on intelligent systems with screw terminals for power (+ and -) and remote annunciator connections.
  • Standards: certified UL, ULC, FM and CSFM. Check these against your specification.

Frequently asked questions

Which detectors does the B501AP take?

System Sensor 200 Series detectors, isolated and non-isolated. Check your detector's own documentation for this base.

Can the detector be locked in place?

Yes. Break off the plastic tab to enable the tamper resistant feature, and the detector then cannot be removed without a suitable tool.

What size wire does it take?

24 to 12 AWG, on SEMS screw connections. AWG is a wire gauge, where a lower number means a thicker wire.

What colours is this base made in?

This code is pure white. B501AP-BK in black and B501AP-IV in ivory are separate codes.

Is it approved to EN54?

It is certified UL, ULC, FM and CSFM. Check the approvals you need against the unit's documentation before specifying it.

£ 3 95
RRP: £4.74 Save £0.79
Google Top Quality Store · Rated Exceptional
Ships from United Kingdom
28 days hassle free returns
Secure payment transactions
Price
£3.95 Incl. VAT £4.74
Add a WME Product Care Plan Includes warranty, replacement and repairs backed by WME
Why add a product care plan:
  • Full breakdown support
  • Full replacement if we can't repair your product within 10 days
  • All parts, labour and callouts included if necessary
  • Extended manufacturer warranty with faster turn arounds
  • Excludes accidental & cosmetic damages
By selecting one of these plans you agree to purchase WME Care Plan. Please read the Terms and Important information to ensure WME Care Plan is right for you. Compare prices of extended warranties for electrical goods at www.compareextendedwarranties.co.uk
WME Care
Technical Details
Specifications
Brand
System Sensor
Model
B501AP
Manufacturer Part Number (MPN)
B501AP
Product type
Analogue sensor base
Colour
Pure white
Base format
Four-inch flangeless mounting base
Designed for
System Sensor 200 Series detectors
Detector types
Isolated and non-isolated detectors
Intended systems
Intelligent systems with screw terminals for power (+ and -) and remote annunciator connections
Wiring connection
SEMS screws
Wire size
24 to 12 AWG
Address identification
Address identification label
Tamper resistance
Enabled by breaking off a plastic tab
Certifications
UL, ULC, FM, CSFM

Specifications

Brand System Sensor
Model B501AP
Manufacturer Part Number (MPN) B501AP
Product type Analogue sensor base
Colour Pure white
Base format Four-inch flangeless mounting base
Designed for System Sensor 200 Series detectors
Detector types Isolated and non-isolated detectors
Intended systems Intelligent systems with screw terminals for power (+ and -) and remote annunciator connections
Wiring connection SEMS screws
Wire size 24 to 12 AWG
Address identification Address identification label
Tamper resistance Enabled by breaking off a plastic tab
Certifications UL, ULC, FM, CSFM

System Sensor B501AP analogue detector base, top view

Notifier System Sensor Smoke Detector Base, Analogue, Pure White, 200 Series B501AP

What this base does

A detector base is the fixed part of a fire detector. The cables end here and the head plugs in, so a head can be taken off for service without disturbing the wiring.

This one is an analogue base. On an analogue addressable system, each device reports to the panel, so the panel can point to the one in alarm.

How it works

  • Isolated and non-isolated: the same base takes both. An isolated detector has a built-in part that cuts off a short section of a loop if a short circuit happens.
  • Address label: write the device's address on the label, or use the break-off tag, so it can be read from the base once the head is off.
  • Remote annunciator: this is a remote indicator or repeat light. The base is intended for systems with screw terminals for that connection.

What the figures mean in practice

  • 24 to 12 AWG: this is an American wire gauge range. 12 AWG is about 3.3mm² and 24 AWG about 0.2mm², so normal UK fire cable sizes usually fall within it.
  • Four-inch: measure against any existing box or bracket before you first fix.

Installing it

  • Tamper tab: the feature is enabled by breaking off the tab, so decide before fitting. Keep a suitable tool for later maintenance.
  • Wiring diagram: work from the maker's installation and wiring diagram.
  • Who does it: fire alarm installation and commissioning are work for a competent person.

Planning your system

Allow one base per detector position, and order the heads separately. Multiple accessory options provide mounting flexibility, so check whether your ceiling needs one.

The system needs an addressable panel running the matching protocol, the language a panel and its devices share. The commercial fire alarm system guide explains why that comes first.

Browse more fire alarm accessories and components.

Approvals explained

  • UL and ULC: product safety marks used in the United States and Canada.
  • FM and CSFM: an American approvals body, and the California State Fire Marshal's approval.
  • What that means here: these are North American approvals. If a UK specification asks for a particular approval, confirm it before ordering.
System Sensor B501AP analogue detector base, top view
Notifier

Notifier System Sensor Smoke Detector Base, Analogue, Pure White, 200 Series B501AP

£3.95 £4.74

The Notifier System Sensor B501AP is a pure white analogue sensor base for System Sensor 200 Series detectors. It suits installers working on intelligent fire alarm systems. It has SEMS screw connections, takes both isolated and non-isolated detectors, and carries an address identification label.

Key features

For installers

Frequently asked questions

Which detectors does the B501AP take?

System Sensor 200 Series detectors, isolated and non-isolated. Check your detector's own documentation for this base.

Can the detector be locked in place?

Yes. Break off the plastic tab to enable the tamper resistant feature, and the detector then cannot be removed without a suitable tool.

What size wire does it take?

24 to 12 AWG, on SEMS screw connections. AWG is a wire gauge, where a lower number means a thicker wire.

What colours is this base made in?

This code is pure white. B501AP-BK in black and B501AP-IV in ivory are separate codes.

Is it approved to EN54?

It is certified UL, ULC, FM and CSFM. Check the approvals you need against the unit's documentation before specifying it.