Nittan UB-6-EV Smoke Detector Base, Indoor Mounting Base, 10-38V F03_83521

£ 2 43
(Incl. VAT) RRP: £2.92
Save £0.49

About this product

The Nittan F03_83521 is a UB-6-EV smoke detector base, an indoor mounting base for Nittan detectors. It suits installers on new work and anyone replacing a base. It has terminations for conventional, addressable and addressable with isolator detectors, and an operating voltage of 10 to 38V d.c.

Key features

  • Wiring for more than one system type – separate terminations for conventional and addressable detectors
  • Also wired for isolator detectors – separate terminations for an addressable detector with isolator
  • Option of a repeat light – a RIL (remote indicator) termination at 2mA
  • Screen connection built in – terminal 4 is the screen in every wiring arrangement
  • Slim on the ceiling – ∅ 104.50mm x 15.00mm
  • Light and simple – 52g, in ABS plastic

For installers

  • Power: operating voltage 10 to 38V d.c.
  • Mounting: indoor mounting base, ∅ 104.50mm x 15.00mm.
  • Cabling, conventional: 1 = –VE In, 6 = –VE Out, 3 = +VE In/Out, 5 = RIL –VE 2mA, 4 = Screen.
  • Cabling, addressable: 1 = +VE In/Out, 6 = –VE In/Out, 3 = RIL –VE 2mA, 4 = Screen, 2 = AUX –VE.
  • Compatibility: check that your detector's own documentation lists the UB-6-EV.
  • Standards: complies with EN54-5 and 7, the heat and smoke detector standards. EMC conformance to BSEN50130-4. Check the detector's own documentation for the head you plan to fit.

Frequently asked questions

Is this a conventional or addressable base?

It is for both. Terminations differ for conventional, addressable and addressable with isolator detectors.

Which detectors fit the UB-6-EV?

Check that the detector's own documentation lists the UB-6-EV before ordering.

Can a remote indicator be wired to it?

Yes. There is a RIL –VE termination at 2mA, on terminal 5 for conventional wiring and terminal 3 for addressable wiring.

How big is the base?

∅ 104.50mm x 15.00mm, and it weighs 52g.

Can it be fitted outdoors?

No. It is an indoor mounting base, with relative humidity of ≤ RH95% non-condensing.

£ 2 43
RRP: £2.92 Save £0.49
Google Top Quality Store · Rated Exceptional
Ships from United Kingdom
28 days hassle free returns
Secure payment transactions
Price
£2.43 Incl. VAT £2.92
Add a WME Product Care Plan Includes warranty, replacement and repairs backed by WME
Why add a product care plan:
  • Full breakdown support
  • Full replacement if we can't repair your product within 10 days
  • All parts, labour and callouts included if necessary
  • Extended manufacturer warranty with faster turn arounds
  • Excludes accidental & cosmetic damages
By selecting one of these plans you agree to purchase WME Care Plan. Please read the Terms and Important information to ensure WME Care Plan is right for you. Compare prices of extended warranties for electrical goods at www.compareextendedwarranties.co.uk
WME Care
Technical Details
Specifications
Brand
Nittan
Model
F03_83521
Manufacturer Part Number (MPN)
F03_83521
Also listed as
UB-6-EV
Maker's part number
UB-6-EV
Description
Mounting base for Detectors
Device type
Indoor mounting base
Operating voltage
10 to 38V d.c.
Operating temperature
– 10°C to + 55°C
Storage temperature
– 25°C to + 70°C
Relative humidity
≤ RH95% non-condensing
Material
ABS
Dimensions
∅ 104.50mm x 15.00mm
Mass
52g
EMC conformance
BSEN50130-4
CE conformity
Yes
Conventional terminations
1 = –VE In; 6 = –VE Out; 3 = +VE In/Out; 5 = RIL –VE 2mA; 4 = Screen
Addressable terminations
1 = +VE In/Out; 6 = –VE In/Out; 3 = RIL –VE 2mA; 4 = Screen; 2 = AUX –VE
Addressable detector with isolator terminations
1 = +VE In/Out; 6 = –VE In; 5 = –VE Out (SCI Only); 3 = RIL –VE 2mA; 4 = Screen; 2 = AUX –VE
Dimensions
Dimensions
∅ 104.50mm x 15.00mm

Specifications

Brand Nittan
Model F03_83521
Manufacturer Part Number (MPN) F03_83521
Also listed as UB-6-EV
Maker's part number UB-6-EV
Description Mounting base for Detectors
Device type Indoor mounting base
Operating voltage 10 to 38V d.c.
Operating temperature – 10°C to + 55°C
Storage temperature – 25°C to + 70°C
Relative humidity ≤ RH95% non-condensing
Material ABS
Dimensions ∅ 104.50mm x 15.00mm
Mass 52g
EMC conformance BSEN50130-4
CE conformity Yes
Conventional terminations 1 = –VE In; 6 = –VE Out; 3 = +VE In/Out; 5 = RIL –VE 2mA; 4 = Screen
Addressable terminations 1 = +VE In/Out; 6 = –VE In/Out; 3 = RIL –VE 2mA; 4 = Screen; 2 = AUX –VE
Addressable detector with isolator terminations 1 = +VE In/Out; 6 = –VE In; 5 = –VE Out (SCI Only); 3 = RIL –VE 2mA; 4 = Screen; 2 = AUX –VE

Dimensions

Dimensions ∅ 104.50mm x 15.00mm

Nittan F03_83521 UB-6-EV smoke detector base, angled view

Nittan UB-6-EV Smoke Detector Base, Indoor Mounting Base, 10-38V F03_83521

What this base does

A detector base is the fixed part of a fire detector. The cables end here and the detector head fits on to it, so a head can be removed for service without disturbing the wiring.

This Nittan base carries the EVOLUTION name, and it can be wired for three kinds of detector circuit.

How the wiring differs

  • Conventional: the negative side breaks between In and Out, on terminals 1 and 6. The positive stays common on terminal 3.
  • Addressable: both polarities are common, with terminal 1 for positive and terminal 6 for negative, and terminal 2 becomes AUX –VE.
  • With an isolator: the negative splits again between terminals 6 and 5, and terminal 5 is marked SCI Only.
  • What an isolator is: it cuts off a short section of a loop if a short circuit happens, so the rest keeps working.

What the figures mean in practice

  • 15.00mm height: this is what the base adds to the ceiling before a head goes on. Allow for the head as well when checking clearance.
  • Indoor rating: the working range of – 10°C to + 55°C and non-condensing humidity limit rule out damp or very cold spaces.
  • 2mA remote indicator: add this to the circuit's load if you fit a repeat light.

Installing it

  • Use the right wiring: terminal 3 changes job between conventional and addressable wiring, so match the wiring to your circuit before first fix.
  • Screen: terminal 4 takes the screen in all three arrangements.
  • Testing: prove continuity and polarity of each zone or loop before any detector heads go on.

Planning your system

Allow one base per detector position, and order the heads separately. Take the fit from the head's own documentation.

An addressable job also needs a panel running the matching protocol, the language a panel and its devices share. The commercial fire alarm system guide explains why that comes first.

Standards explained

It complies with EN54-5 and 7, the heat and smoke detector standards. Check the detector's own documentation for the head you plan to fit.

  • BSEN50130-4: a standard covering electromagnetic compatibility, or how well equipment copes with electrical interference, for alarm systems.
Nittan F03_83521 UB-6-EV smoke detector base, angled view
Nittan

Nittan UB-6-EV Smoke Detector Base, Indoor Mounting Base, 10-38V F03_83521

£2.43 £2.92

The Nittan F03_83521 is a UB-6-EV smoke detector base, an indoor mounting base for Nittan detectors. It suits installers on new work and anyone replacing a base. It has terminations for conventional, addressable and addressable with isolator detectors, and an operating voltage of 10 to 38V d.c.

Key features

For installers

Frequently asked questions

Is this a conventional or addressable base?

It is for both. Terminations differ for conventional, addressable and addressable with isolator detectors.

Which detectors fit the UB-6-EV?

Check that the detector's own documentation lists the UB-6-EV before ordering.

Can a remote indicator be wired to it?

Yes. There is a RIL –VE termination at 2mA, on terminal 5 for conventional wiring and terminal 3 for addressable wiring.

How big is the base?

∅ 104.50mm x 15.00mm, and it weighs 52g.

Can it be fitted outdoors?

No. It is an indoor mounting base, with relative humidity of ≤ RH95% non-condensing.