C-TEC CAST-PRO Smoke and Heat Multisensor Detector, Addressable CP414

£ 48 12
(Incl. VAT) RRP: £57.74
Save £9.62

About this product

The C-TEC CP414 is a CAST-PRO addressable smoke and heat multisensor fire detector for C-TEC's ZFP CAST protocol panels. It suits installers who want fast detection with strong tolerance to false alarms. It has 8 detection modes, an onboard loop isolator and certification to EN54-5, 7, 17 & 29.

Key features

  • Two ways to detect fire – smoke and heat multisensor detection
  • Fewer false alarms – MASC™ chamber and AFFIRM™ algorithms
  • Stays accurate as it ages – drift compensation functionality
  • Tune it to the room – 8 detection modes, Mode 7 by default
  • Contains loop faults – onboard short circuit loop isolator
  • Easy to spot in alarm – two ultra-bright red LED strips with 360º visibility
  • Light on the loop – 570uA typical quiescent current @ 40V DC, <1mA in alarm

For installers

  • Power: 22 to 40V DC from the loop; 2-wire, polarity sensitive; quiescent current 570uA @ 40V; alarm current <1mA.
  • Mounting: requires a CA408 CAST base. 105mm diameter x 65mm deep in the base; 173g in base.
  • Cabling: via the CA408 base, terminals 1 +Ve IN, 2 +Ve OUT, 3 Remote LED +Ve, 4 and 5 0V, 6 and 7 Screen.
  • Compatibility: C-TEC's ZFP CAST addressable fire alarm systems.
  • Standards: certified to EN54-5, 7, 17 & 29 (KIWA), CPR number 0063-CPR-242190021; IP21C.

Frequently asked questions

Which panels does it work with?

C-TEC's ZFP CAST addressable fire alarm systems.

Does it come with a base?

It requires a CA408 CAST base. The CA408R relay base is the alternative where a relay is needed.

Does it have a sounder or beacon?

No. Sound output and VAD category are N/A for this detector.

How many detection modes are there?

8 detection modes; the default for this device is Mode 7.

Does it have a loop isolator?

Yes. It has an onboard short circuit loop isolator, and it is certified to EN54-5, 7, 17 & 29.

£ 48 12
RRP: £57.74 Save £9.62
Google Top Quality Store · Rated Exceptional
Ships from United Kingdom
28 days hassle free returns
Secure payment transactions
Price
£48.12 Incl. VAT £57.74
Add a WME Product Care Plan Includes warranty, replacement and repairs backed by WME
Why add a product care plan:
  • Full breakdown support
  • Full replacement if we can't repair your product within 10 days
  • All parts, labour and callouts included if necessary
  • Extended manufacturer warranty with faster turn arounds
  • Excludes accidental & cosmetic damages
By selecting one of these plans you agree to purchase WME Care Plan. Please read the Terms and Important information to ensure WME Care Plan is right for you. Compare prices of extended warranties for electrical goods at www.compareextendedwarranties.co.uk
WME Care
Technical Details
Specifications
Brand
C-TEC
Model
CP414
Manufacturer Part Number (MPN)
CP414
Type
Multisensor (heat & smoke) detection
Range
CAST-PRO
Protocol
CAST
Compatibility
C-TEC ZFP CAST addressable fire alarm systems
Sensitivity
8 detection modes (default Mode 7)
Supply wiring
2-wire, polarity sensitive
Supply/operating voltage
22 to 40V DC
Quiescent current
570uA @ 40V
Alarm current (Imax at Vmin)
<1mA
Alarm current (Iavg at Vmin)
<1mA
Sound pressure level
N/A
VAD category & coverage
N/A
Indicators
2 red LED indicator strips, 8mm x 2mm, 360º visibility; optional remote LED
Isolator
Onboard short circuit loop isolator
Connections (via CA408 base)
1 +Ve IN (analogue switch); 2 +Ve OUT (analogue switch); 3 Remote LED +Ve; 4 0V; 5 0V; 6 Screen; 7 Screen
Dimensions
105mm diameter x 48mm deep (detector only); 105mm diameter x 65mm deep (in base)
Weight
119g (not in base); 173g (in base)
IP rating
IP21C
Max relative humidity
95% (non-condensing)
Base
Requires CA408 CAST base; CA408R relay base as alternative
Approvals
EN54-5, 7, 17 & 29 (KIWA); CPR number 0063-CPR-242190021
Dimensions
Dimensions
105mm diameter x 48mm deep (detector only)

Specifications

Brand C-TEC
Model CP414
Manufacturer Part Number (MPN) CP414
Type Multisensor (heat & smoke) detection
Range CAST-PRO
Protocol CAST
Compatibility C-TEC ZFP CAST addressable fire alarm systems
Sensitivity 8 detection modes (default Mode 7)
Supply wiring 2-wire, polarity sensitive
Supply/operating voltage 22 to 40V DC
Quiescent current 570uA @ 40V
Alarm current (Imax at Vmin) <1mA
Alarm current (Iavg at Vmin) <1mA
Sound pressure level N/A
VAD category & coverage N/A
Indicators 2 red LED indicator strips, 8mm x 2mm, 360º visibility; optional remote LED
Isolator Onboard short circuit loop isolator
Connections (via CA408 base) 1 +Ve IN (analogue switch); 2 +Ve OUT (analogue switch); 3 Remote LED +Ve; 4 0V; 5 0V; 6 Screen; 7 Screen
Dimensions 105mm diameter x 48mm deep (detector only); 105mm diameter x 65mm deep (in base)
Weight 119g (not in base); 173g (in base)
IP rating IP21C
Max relative humidity 95% (non-condensing)
Base Requires CA408 CAST base; CA408R relay base as alternative
Approvals EN54-5, 7, 17 & 29 (KIWA); CPR number 0063-CPR-242190021

Dimensions

Dimensions 105mm diameter x 48mm deep (detector only)

C-TEC CP414 CAST-PRO smoke and heat multisensor, angled view

C-TEC CAST-PRO Smoke and Heat Multisensor Detector, Addressable CP414

Overview

A multisensor looks for both smoke and heat, so it can confirm a real fire with two signals instead of one. This C-TEC detector belongs to the CAST-PRO range for ZFP addressable panels.

It is the detector-only version, with no sounder or beacon. Where an alarm sound or a visual alarm device is needed at the same point, plan a separate device for it.

How it works

  • MASC™ chamber: a miniature advanced smoke detection chamber that samples the air for smoke.
  • AFFIRM™ algorithms: C-TEC's algorithms give tolerance to false alarms.
  • Drift compensation: dust slowly builds up in any chamber, and the detector adjusts for it over time.

Where to use it

It works at up to 95% relative humidity, non-condensing, and is rated IP21C. That makes it an indoor ceiling device for dry spaces.

It has 8 detection modes, with Mode 7 as the default.

What the figures mean in practice

  • 570uA quiescent: the standing current @ 40V, which goes into the loop load calculation for the panel.
  • Onboard isolator: a short circuit on the cable is cut off at the nearest devices, so the rest of the loop keeps working.
  • IP21C: protected against fingers and against vertically falling drops of water, so keep it away from wet areas.

Installing it

The detector needs the C-TEC CA408 CAST base, which has an integrated locking mechanism and ID tag. Where a relay output is wanted at the head, use the C-TEC CA408R relay base instead.

The wiring is 2-wire and polarity sensitive, so check polarity at every base before fitting heads.

Planning your system

It works only with C-TEC's ZFP CAST addressable systems, so choose the panel from the C-TEC fire panels range. The guide to commercial fire alarm systems explains why addressable protocols must match.

Other CAST and CAST-PRO heads are among the C-TEC detectors. This guide to heat detectors explains where heat or multisensor detection beats smoke alone.

Standards and ratings explained

  • EN54-5, 7, 17 & 29: the parts of EN54 covering point heat detectors, point smoke detectors, short-circuit isolators and multi-sensor fire detectors.
  • CPR number: 0063-CPR-242190021 is the certificate reference, and KIWA certified the detector to EN54-5, 7, 17 & 29.
C-TEC CP414 CAST-PRO smoke and heat multisensor, angled view
C-TEC

C-TEC CAST-PRO Smoke and Heat Multisensor Detector, Addressable CP414

£48.12 £57.74

The C-TEC CP414 is a CAST-PRO addressable smoke and heat multisensor fire detector for C-TEC's ZFP CAST protocol panels. It suits installers who want fast detection with strong tolerance to false alarms. It has 8 detection modes, an onboard loop isolator and certification to EN54-5, 7, 17 & 29.

Key features

For installers

Frequently asked questions

Which panels does it work with?

C-TEC's ZFP CAST addressable fire alarm systems.

Does it come with a base?

It requires a CA408 CAST base. The CA408R relay base is the alternative where a relay is needed.

Does it have a sounder or beacon?

No. Sound output and VAD category are N/A for this detector.

How many detection modes are there?

8 detection modes; the default for this device is Mode 7.

Does it have a loop isolator?

Yes. It has an onboard short circuit loop isolator, and it is certified to EN54-5, 7, 17 & 29.

View product